Two-way thermal release valve SYR 5067 - 3/4 with pressure reducing valve
Price: GBP295.90
Notify me of availability

Description

Field of application: The thermal safety combination type 5067 prevents excess temperatures in solid fuel fired boilers. This protective device can be attached to solid fuel boilers without integrated hot water storage vessels.

Installation and function

Connect the inlet of the thermal safety combination to the water supply. The outlet of the inlet valve leads to the heating return line. Connect the radiator supply line to the outlet valve of the thermal safety combination. The outlet of the inlet valve leads through the integrated tundish to the drain.

Install the temperature probe at the hottest spot, preferably in the upper part of the boiler. Only use the immersion sleeve enclosed in the delivery to ensure correct temperature measurements. Set the pressure reducing valve to a pressure below the highest admissible operating pressure of the heating system in order to prevent a response of the diaphragm pressure relief valve, which is imperatively required for the protection of the boiler against excess pressure.

When the temperature exceeds the set response temperature, the following operational sequence is started: The seat of the inlet valve opens at a temperature of about 90°C in order to keep the pressure stable in the heating system. The outlet valve opens at 97°C. When the outlet valve is opened, hot water is drained from the heating system and cold water can enter from the supply pipe, which will cool down the boiler. When the boiler temperature has dropped to 94°C, the outlet valve closes. The pressure reducing valve ensures with the inlet valve still open that the heating system operates at correct service pressure. When the temperature has reached 88°C, the inlet valve closes.

The thermal safety combination includes the following components (in direction of flow):

  1. check valve
  2. pressure reducing valve
  3. temperature activated inlet valve
  4. temperature activated outlet valve
  5. temperature probe
SYR 5067

Usage for boilers with nominal power up to 100 kW

Pressure regulator pressure: 1,2 bar (Factory setting)
Maximum input water pressure: 16 bar
Minimum required water inlet pressure: 2,3 bar
Maximum operating temperature: 135°C
Mass 1,5kg

Opening temperature Closing temperature
Filling valve 90°C +0/-2°C 88°C +0/-2°C
Ejection valve 97°C +0/-2°C 94°C +0/-2°C

Water flow through thermal protection 5067 at specified temperature and setpoint of pressure reducer, with assumed cold water inlet pressure 8 bar:

Pressure regulator setting [bar] Flow Q [m3/h] at 100°C Flow Q [m3/h] at 110°C
1,5 0,58 1,35
2,5 0,73 1,95
3,0 0,82 2,17
5,0 1,10 2,90
SYR 5067

Product Details

Reference
21329
Condition
New
Product type
Thermostatic valve
Valve
Weight [ kg ]
1.50
Thread type
3⁄4''
Installation
Internal
Vertical
Max. working temperature [ °C ]
135
Opening temperature [ °C ]
97
Flow Rate [ l/h ]
2900

Comments